Wire Size Calculator
The smallest copper or aluminum wire gauge for your amps, distance and voltage drop.
From the panel to the load.
copper at 60 °C, 3% max voltage drop
- Wire ampacity
- 30 A
- Voltage drop
- 2.48 V
- Voltage drop %
- 2.07%
- Size by ampacity only
- 12 AWG
How it works
Voltage drop = 2 × distance (ft) × amps × resistance (Ω per 1,000 ft) ÷ 1,000 (three-phase: √3 instead of 2, line-to-line voltage)
Example: Load current 20 · Voltage 120 · One-way distance 100 ft · Max voltage drop 3% → 8 AWG (wire ampacity: 40 A, voltage drop: 3.11 V, voltage drop %: 2.59%, size by ampacity only: 12 AWG).
The calculator starts from the smallest gauge whose ampacity covers your load, using NEC Table 310.16 and the small-conductor limits of NEC 240.4(D): 14 AWG copper is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A. For a continuous load that runs three hours or more, the wire must carry 125% of the current.
It then checks the voltage drop over the run with the resistance of each gauge at 75 °C (NEC Chapter 9, Table 8). If the drop is above your limit, it moves up one size until it fits. The NEC recommends no more than 3% on a branch circuit and 5% in total.
NM-B (Romex) cable is sized with the 60 °C column. Results assume no more than three current-carrying conductors and a 30 °C ambient temperature; hot attics, bundled cables and local codes can require a larger wire. On AC feeders of 1/0 and larger, reactance adds roughly 15 to 30% to the voltage drop, so leave extra margin. The breaker must not exceed the wire ampacity, a wire upsized for voltage drop needs a proportionally larger ground (NEC 250.122(B)), and motors, air conditioners and EV chargers are sized from their nameplate. Have a licensed electrician check any new circuit.
Questions
What size wire do I need for a 20 amp circuit?
12 AWG copper for a normal run. Past about 45 feet at a full 20 A load on 120 V, voltage drop pushes it to 10 AWG to stay under 3%.
What size wire for 30 amps?
10 AWG copper, the smallest size the NEC allows on a 30 A breaker. Long runs may need 8 AWG.
What size wire for 50 amps?
6 AWG copper with NM-B cable (60 °C, 55 A), or 8 AWG copper in conduit with 75 °C terminals (50 A).
How much voltage drop is acceptable?
The NEC recommends no more than 3% on a branch circuit and 5% from the service to the farthest outlet.
Is aluminum wire bigger than copper for the same amps?
Yes. Aluminum conducts about 61% as well as copper, so it usually needs a wire one or two sizes larger. In practice aluminum building wire starts at 8 AWG.