Voltage Drop Calculator

Voltage drop, percent drop and voltage at the load for a copper or aluminum wire run.

Conductor
System
V
A
ft
Voltage drop3.3%

over 3%: use a larger wire or a shorter run

Drop in volts
3.96 V
Voltage at the load
116 V
Longest run under 3%
45.5 ft
Wire resistance (75 °C)
1.98 Ω per 1,000 ft

How it works

Voltage drop = 2 × distance (ft) × amps × resistance (Ω per 1,000 ft) ÷ 1,000 (three-phase: √3 instead of 2)

Example: Wire size 12 · Voltage 120 · Load current 20 · One-way distance 50 ft → 3.3% (drop in volts: 3.96 V, voltage at the load: 116 V, longest run under 3%: 45.5 ft, wire resistance (75 °c): 1.98 Ω per 1,000 ft).

Current flows out and back, so a single-phase or DC circuit loses voltage over twice the one-way distance. Multiply that length by the current and by the resistance of the wire, taken from NEC Chapter 9, Table 8 at 75 °C: 1.98 ohms per 1,000 feet for 12 AWG copper, 1.24 for 10 AWG.

A 20 A load at the end of 50 feet of 12 AWG copper loses 2 × 50 × 20 × 1.98 ÷ 1,000 = 3.96 volts, or 3.3% of 120 V. The NEC recommends no more than 3% on a branch circuit and 5% from the service to the farthest outlet.

For three-phase circuits use √3 (1.732) instead of 2 and divide by the line-to-line voltage. On AC feeders of 1/0 and larger, reactance adds roughly 15 to 30%. To pick a wire that meets both ampacity and voltage drop, use the wire size calculator.

Questions

What is an acceptable voltage drop?

3% on a branch circuit and 5% in total from the service, as recommended by the National Electrical Code.

How far can I run 12 gauge wire on a 20 amp circuit?

About 45 feet at a full 20 A load on 120 V before the drop passes 3%; at 240 V, about 90 feet.

Does voltage drop depend on the wire length?

Yes, it grows in proportion to the length: double the run and the drop doubles.

How do I reduce voltage drop?

Use a larger wire (a smaller AWG number), copper instead of aluminum, a higher voltage or a shorter run.