Voltage Drop Calculator
Voltage drop, percent drop and voltage at the load for a copper or aluminum wire run.
over 3%: use a larger wire or a shorter run
- Drop in volts
- 3.96 V
- Voltage at the load
- 116 V
- Longest run under 3%
- 45.5 ft
- Wire resistance (75 °C)
- 1.98 Ω per 1,000 ft
How it works
Voltage drop = 2 × distance (ft) × amps × resistance (Ω per 1,000 ft) ÷ 1,000 (three-phase: √3 instead of 2)
Example: Wire size 12 · Voltage 120 · Load current 20 · One-way distance 50 ft → 3.3% (drop in volts: 3.96 V, voltage at the load: 116 V, longest run under 3%: 45.5 ft, wire resistance (75 °c): 1.98 Ω per 1,000 ft).
Current flows out and back, so a single-phase or DC circuit loses voltage over twice the one-way distance. Multiply that length by the current and by the resistance of the wire, taken from NEC Chapter 9, Table 8 at 75 °C: 1.98 ohms per 1,000 feet for 12 AWG copper, 1.24 for 10 AWG.
A 20 A load at the end of 50 feet of 12 AWG copper loses 2 × 50 × 20 × 1.98 ÷ 1,000 = 3.96 volts, or 3.3% of 120 V. The NEC recommends no more than 3% on a branch circuit and 5% from the service to the farthest outlet.
For three-phase circuits use √3 (1.732) instead of 2 and divide by the line-to-line voltage. On AC feeders of 1/0 and larger, reactance adds roughly 15 to 30%. To pick a wire that meets both ampacity and voltage drop, use the wire size calculator.
Questions
What is an acceptable voltage drop?
3% on a branch circuit and 5% in total from the service, as recommended by the National Electrical Code.
How far can I run 12 gauge wire on a 20 amp circuit?
About 45 feet at a full 20 A load on 120 V before the drop passes 3%; at 240 V, about 90 feet.
Does voltage drop depend on the wire length?
Yes, it grows in proportion to the length: double the run and the drop doubles.
How do I reduce voltage drop?
Use a larger wire (a smaller AWG number), copper instead of aluminum, a higher voltage or a shorter run.