Conduit Fill Calculator
How many THHN wires fit in EMT or PVC conduit, the fill percentage and the smallest size.
Count the ground wire too.
your 4 wires fit: 17.5% fill
- Fill with your wires
- 17.5%
- Allowed fill
- 40%
- Smallest conduit for your wires
- 1/2 in
- Wire area
- 0.0532 sq in
- Conduit area
- 0.304 sq in
How it works
Max wires = conduit area × 40% ÷ wire area (round up when the decimal is 0.8 or more)
Example: Conduit emt · Trade size 1/2 · Wire size (THHN) 12 · Number of wires 4 → 9 wires (fill with your wires: 17.5%, allowed fill: 40%, smallest conduit for your wires: 1/2 in, wire area: 0.0532 sq in, conduit area: 0.304 sq in).
NEC Chapter 9 limits conduit fill to 53% of the inside area for one wire, 31% for two and 40% for three or more. Divide 40% of the conduit area (Table 4) by the area of one wire with its insulation (Table 5). When all wires are the same size, a result of 0.8 or more may be rounded up (Note 7).
A 1/2 in EMT has 0.304 square inches inside, so 40% is 0.122. A 12 AWG THHN wire takes 0.0133, so 9 wires fit; 14 AWG fits 12 and 10 AWG fits 5, the same counts as the NEC Annex C tables.
Count every conductor, including the equipment ground. More than three current-carrying conductors in a raceway also reduce their ampacity (NEC 310.15(C)(1)), and nipples under 24 in may be filled to 60%.
Questions
How many 12 gauge wires can go in 1/2 EMT?
9 THHN conductors of 12 AWG; 16 in 3/4 in EMT and 26 in 1 in EMT.
How many 14 gauge wires in 1/2 inch conduit?
12 THHN conductors of 14 AWG in 1/2 in EMT, or 11 in 1/2 in PVC Schedule 40.
What is the maximum conduit fill?
40% of the inside area for three or more wires, 31% for two and 53% for one (NEC Chapter 9, Table 1).
Does the ground wire count in conduit fill?
Yes. Equipment grounding conductors count toward fill, though not toward the ampacity adjustment for current-carrying conductors.