Conduit Fill Calculator

How many THHN wires fit in EMT or PVC conduit, the fill percentage and the smallest size.

Conduit

Count the ground wire too.

Maximum wires9 wires

your 4 wires fit: 17.5% fill

Fill with your wires
17.5%
Allowed fill
40%
Smallest conduit for your wires
1/2 in
Wire area
0.0532 sq in
Conduit area
0.304 sq in

How it works

Max wires = conduit area × 40% ÷ wire area (round up when the decimal is 0.8 or more)

Example: Conduit emt · Trade size 1/2 · Wire size (THHN) 12 · Number of wires 4 → 9 wires (fill with your wires: 17.5%, allowed fill: 40%, smallest conduit for your wires: 1/2 in, wire area: 0.0532 sq in, conduit area: 0.304 sq in).

NEC Chapter 9 limits conduit fill to 53% of the inside area for one wire, 31% for two and 40% for three or more. Divide 40% of the conduit area (Table 4) by the area of one wire with its insulation (Table 5). When all wires are the same size, a result of 0.8 or more may be rounded up (Note 7).

A 1/2 in EMT has 0.304 square inches inside, so 40% is 0.122. A 12 AWG THHN wire takes 0.0133, so 9 wires fit; 14 AWG fits 12 and 10 AWG fits 5, the same counts as the NEC Annex C tables.

Count every conductor, including the equipment ground. More than three current-carrying conductors in a raceway also reduce their ampacity (NEC 310.15(C)(1)), and nipples under 24 in may be filled to 60%.

Questions

How many 12 gauge wires can go in 1/2 EMT?

9 THHN conductors of 12 AWG; 16 in 3/4 in EMT and 26 in 1 in EMT.

How many 14 gauge wires in 1/2 inch conduit?

12 THHN conductors of 14 AWG in 1/2 in EMT, or 11 in 1/2 in PVC Schedule 40.

What is the maximum conduit fill?

40% of the inside area for three or more wires, 31% for two and 53% for one (NEC Chapter 9, Table 1).

Does the ground wire count in conduit fill?

Yes. Equipment grounding conductors count toward fill, though not toward the ampacity adjustment for current-carrying conductors.