kW to Amps Calculator
Convert kilowatts to amps for DC, single-phase or three-phase circuits.
1 for heaters; about 0.8–0.9 for motors and generators.
10 kW at 240 V, single-phase
- In watts
- 10,000 W
- Apparent power
- 10 kVA
- Continuous load × 125%
- 52.1 A
How it works
Amps = kW × 1,000 ÷ volts (DC) · ÷ (volts × PF) single-phase · ÷ (1.732 × volts × PF) three-phase
Example: Power 10 · Voltage 240 · Circuit single · Power factor 1 → 41.67 A (in watts: 10,000 W, apparent power: 10 kVA, continuous load × 125%: 52.1 A).
Multiply the kilowatts by 1,000 for watts, then divide by the voltage. A 10 kW single-phase heater on 240 V draws 10,000 ÷ 240 = 41.7 A. The same load on a 208 V three-phase supply draws 10,000 ÷ (1.732 × 208) = 27.8 A per phase.
For motors, generators and other inductive loads, divide also by the power factor: a 10 kW motor at 0.85 PF on 240 V single-phase draws 49 A. The apparent power, in kVA, is kW ÷ PF.
Breakers and wires for continuous loads (3 hours or more) are sized at 125% of the current: a 41.7 A heater needs at least a 52 A rating, so a 60 A breaker. Use the wire size calculator for the conductor.
Questions
How many amps is 1 kW?
8.3 A at 120 V, 4.2 A at 240 V (single-phase, PF 1).
How many amps is 10 kW at 240 V?
41.7 A single-phase, or 24.1 A three-phase.
How many amps is a 7.2 kW EV charger?
30 A at 240 V.