kVA Calculator
Convert amps to kVA, kVA to amps, and kVA to kW for single-phase or three-phase power.
About 0.8 for generators and motors.
single-phase at 240 V; 19.2 kW at PF 0.8
- Apparent power
- 24 kVA
- Current
- 100 A
- Real power (kVA × PF)
- 19.2 kW
How it works
Single-phase: kVA = V × A ÷ 1,000 · three-phase: kVA = 1.732 × V × A ÷ 1,000 · kW = kVA × PF
Example: Amps → kVA, Current 100 · Voltage (line to line for 3-phase) 240 · Phase single · Power factor 0.8 → 24 kVA (apparent power: 24 kVA, current: 100 A, real power (kva × pf): 19.2 kW).
kVA is apparent power: volts times amps, divided by 1,000. A 100 A single-phase service at 240 V carries up to 24 kVA. On three-phase, multiply also by √3 (1.732) with the line-to-line voltage: 100 A at 208 V three-phase is 36 kVA.
To find the current a transformer or generator can deliver, divide the kVA by the voltage (and by 1.732 on three-phase): a 75 kVA three-phase transformer at 208 V delivers 208 A per phase; at 480 V, 90 A.
Real power, in kW, is kVA times the power factor. Generators are often rated at 0.8 PF, so a 100 kVA generator delivers 80 kW. Size transformers in kVA for the total load, with some margin for motor starting.
Questions
How many amps is 75 kVA?
208 A at 208 V three-phase, 90 A at 480 V three-phase, 312.5 A at 240 V single-phase.
What is the difference between kVA and kW?
kW is real power; kVA is apparent power. kW = kVA × power factor.
How many kVA is a 200 amp service?
48 kVA at 240 V single-phase.