Heat Loss Calculator
Estimate a room’s or home’s heat loss in BTU per hour at your winter design temperature.
Floor area × ceiling height.
0.35 average; 0.2 for a tight new home, 0.7–1 for an old drafty one.
The 99% winter design temperature for your city (ASHRAE).
at a 65 °F difference (4.2 kW)
- Walls
- 4,000 BTU/h
- Windows and doors
- 4,875 BTU/h
- Ceiling
- 2,167 BTU/h
- Air leakage
- 3,276 BTU/h
- In kilowatts
- 4.2 kW
How it works
Q = area ÷ R × ΔT for walls and ceiling · Q = area × U × ΔT for windows · air: 0.018 × volume × ACH × ΔT
Example: Net wall area (without windows) 800 sq ft · Wall R-value 13 · Window and door area 150 sq ft · Windows double · Ceiling area (under the attic) 1,000 sq ft · Ceiling R-value 30 · Heated volume 8,000 cu ft · Air changes per hour 0.35 · Indoor temperature 70 · Outdoor design temperature 5 → 14,318 BTU/h (walls: 4,000 BTU/h, windows and doors: 4,875 BTU/h, ceiling: 2,167 BTU/h, air leakage: 3,276 BTU/h, in kilowatts: 4.2 kW).
Heat flows out through every surface at a rate of U × area × temperature difference, in BTU per hour, where U = 1 ÷ R. Add the air that leaks in and must be heated: 0.018 BTU per cubic foot per °F, times the volume and the air changes per hour.
For the example home at 70 °F inside and 5 °F outside (65 °F difference): 800 sq ft of R-13 walls lose 4,000 BTU/h, 150 sq ft of double-pane windows 4,875, 1,000 sq ft of R-30 ceiling 2,167, and 8,000 cubic feet of air at 0.35 ACH 3,276. Total: about 14,300 BTU/h, or 4.2 kW.
This is a simplified estimate that ignores framing, floors and ducts. Heating equipment is sized with a full ACCA Manual J calculation; use this one to compare upgrades, such as new windows or more attic insulation, and to check that a heater or heat pump is in the right range.
Questions
How do I calculate heat loss?
Q = U × area × ΔT for each surface, plus 0.018 × volume × ACH × ΔT for air leakage.
How much heat does a window lose?
A 15 sq ft double-pane window loses about 490 BTU/h at a 65 °F difference.
What is a design temperature?
The outdoor temperature exceeded 99% of the winter hours in your area, from ASHRAE tables.