Air Changes per Hour Calculator

Air changes per hour from a fan or purifier’s CFM, the CFM needed for a target, or a home’s ventilation rate.

ft
ft
ft
CFM

From the fan or air purifier (CADR for purifiers).

Result8.3 ACH

air changes per hour at this airflow

Room volume
1,440 cu ft
One full air change every
7.2 min
CFM for 5 ACH (CDC goal)
120 CFM

How it works

ACH = CFM × 60 ÷ room volume (cu ft) · CFM = ACH × volume ÷ 60 · ASHRAE 62.2: CFM = 0.03 × floor area + 7.5 × (bedrooms + 1)

Example: ACH from CFM, Room length 15 ft · Room width 12 ft · Ceiling height 8 ft · Airflow 200 → 8.3 ACH (room volume: 1,440 cu ft, one full air change every: 7.2 min, cfm for 5 ach (cdc goal): 120 CFM).

Air changes per hour count how many times the air in a room is replaced, or cleaned, each hour. Multiply the airflow in cubic feet per minute by 60 and divide by the room volume. A 15 × 12 ft room with an 8 ft ceiling holds 1,440 cubic feet; a purifier with a 200 CFM clean air delivery rate gives it 8.3 air changes per hour.

To reach a target, work backwards: the CDC suggests aiming for at least 5 air changes per hour of clean air in occupied rooms, which for that room means 120 CFM.

For a whole house, the ASHRAE 62.2 ventilation standard asks for 0.03 CFM per square foot plus 7.5 CFM per occupant, counted as bedrooms + 1. A 2,000 sq ft, 3-bedroom home needs about 90 CFM of continuous fresh air, separate from bathroom and kitchen exhaust fans.

Questions

How do I calculate air changes per hour?

ACH = CFM × 60 ÷ room volume in cubic feet.

How many air changes per hour do I need?

The CDC suggests at least 5 per hour of clean air in occupied rooms.

How much ventilation does a house need?

0.03 CFM per sq ft plus 7.5 CFM per bedroom + 1 (ASHRAE 62.2): about 90 CFM for 2,000 sq ft and 3 bedrooms.