Duct Size Calculator

The round duct diameter for an airflow in CFM at a chosen friction rate, with air velocity.

CFM
Friction rate
Duct size10 in round duct

for 400 CFM at 0.1 in. w.c. per 100 ft

Calculated diameter
9.83 in
Air velocity in that duct
733 ft/min

How it works

Diameter (in) = (0.109136 × CFM^1.9 ÷ friction rate)^(1 ÷ 5.02)

Example: Airflow 400 · Friction rate 0.1 → 10 in round duct (calculated diameter: 9.83 in, air velocity in that duct: 733 ft/min).

Duct sizing balances airflow against pressure loss. The equal-friction method picks a friction rate, often 0.1 inch of water column per 100 feet for residential supply ducts, and sizes every duct to lose air pressure at that rate. The Wright equation, behind the ASHRAE friction charts for galvanized duct, gives the round diameter for a given CFM.

About 100 CFM needs a 6 inch duct, 400 CFM a 10 inch duct and 1,200 CFM about 16 inches at 0.1 in. w.c. Round up to the next standard size and check the velocity: supply branches usually stay under about 600 to 900 feet per minute to stay quiet.

Flex duct has more friction than metal, so go one size larger; full system design follows ACCA Manual D.

Questions

What size duct for 100 CFM?

A 6 inch round duct at 0.1 in. w.c. per 100 ft.

What size duct for 400 CFM?

A 10 inch round duct at 0.1 in. w.c.; at 0.08 the calculated 10.3 inches rounds up to a standard 12 inch duct.

How many CFM per ton of air conditioning?

About 400 CFM per ton.