Attic Ventilation Calculator

How much attic ventilation you need, and how many feet of ridge vent or box vents.

ft
ft
Code rule
Net free vent area576 sq in

1/300 of the attic floor, half intake and half exhaust

Exhaust (high)
288 sq in
Intake (low, soffits)
288 sq in
Ridge vent (18 sq in/ft)
16 ft
Or box vents (50 sq in)
6 box vents
Continuous soffit vent (9 sq in/ft)
32 ft
Attic floor area
1,200 sq ft

How it works

Net free area (sq in) = attic floor (sq ft) ÷ 300 × 144 · half intake, half exhaust

Example: Attic length 40 ft · Attic width 30 ft · Code rule 300 → 576 sq in (exhaust (high): 288 sq in, intake (low, soffits): 288 sq in, ridge vent (18 sq in/ft): 16 ft, or box vents (50 sq in): 6 box vents, continuous soffit vent (9 sq in/ft): 32 ft, attic floor area: 1,200 sq ft).

Building codes ask for 1 square foot of net free vent area for every 300 square feet of attic floor when 40 to 50% of the vent area is high on the roof, within 3 ft of the ridge, with the rest at the eaves (or, in the coldest climate zones 6 to 8, with a Class I or II vapor retarder on the warm side of the ceiling), and 1 per 150 otherwise. Multiply by 144 for square inches, the unit printed on vent packaging.

A 40 × 30 ft attic (1,200 sq ft) needs 4 sq ft, or 576 sq in, of net free area: 288 sq in of intake at the soffits and 288 sq in of exhaust near the ridge. That is 16 ft of ridge vent at 18 sq in per foot, or 6 box vents of 50 sq in, plus 32 ft of continuous soffit vent at 9 sq in per foot.

Ratings vary by product, so use the net free area printed on your vents. Never mix exhaust types on the same roof (ridge vents with box vents or gable vents): the vents short-circuit and pull air from each other instead of from the soffits.

Questions

How much ventilation does a 1,200 sq ft attic need?

576 sq in of net free area at 1/300: 288 sq in intake and 288 sq in exhaust.

How many box vents do I need?

Divide the exhaust area by the vent rating: 288 sq in ÷ 50 = 6 box vents for a 1,200 sq ft attic.

What is the 1/300 rule?

1 sq ft of net free vent area per 300 sq ft of attic floor, split between intake and exhaust.